aTSE epoxy-resin dry-type transformers

An excellent environmentally friendly alternative: safe operation, minimal maintenance and virtually unlimited installation options, indoors and outdoors. Manufactured in the European Union to IEC 60076 and EN 50588-1.
- Metal parts of aluminium or its alloys.
- Resistant to ambient temperatures up to 55 °C, short circuits, overloads, harmonics and lightning.
- Minimal fire risk thanks to non-flammable insulating materials.
- No liquid cooling, minimal maintenance and a service life of over 25 years.
- Grain-oriented silicon-steel core, aluminium foil windings, PTC or PT100 sensors and off-circuit tap changer.
- Options: monitoring, forced ventilation, anti-theft galvanized steel enclosure and customization.
- Partial tests during manufacture and tests on the complete unit; special tests on request.
| Standard | IEC 60076; ANSI/IEEE on request |
| Type | Dry-type, epoxy resin |
| Rated power | 25 kVA – 12 MVA |
| HV voltage | As required, up to 38.5 kV |
| LV voltage | As required by the customer |
| Frequency | 50 or 60 Hz, as required |
| Vector group | As required by the customer |
| Tapping range | As required by the customer (e.g. ±2 × 2.5 %) |
| Impedance (75 °C) | As required by the customer |
| Winding material | Aluminium / Aluminium |
| Thermal class | F (155 °C) |
| Climatic / environmental class | C2 / E2 |
| Max. ambient temperature | 55 °C |
| Max. altitude | As required (standard design up to 1,000 m a.s.l.) |
| Cooling | AN (optional forced ventilation) |
| Dimensions and weight | Depends on rating and configuration; dimensional drawings on request |
Each unit is built to the parameters the customer requires. Request your specification.
Parameters defined by the customer
Power ratingPrimary and secondary voltagesVector groupFrequencyVoltage regulationImpedanceSite altitude and climateStandardsAccessories and protections
Send enquiry 